Description:
High-quality Kaeser refrigeration dryer with hot gas bypass control, high throughput reliability, Eco-Drain electronic condensate drain, stainless steel plate heat exchanger system with air-to-air heat exchanger and efficient condensate separator. Low overall height and small footprint.
Pressure dew point:
+3°C
Operating pressure:
3 - 16 bar
Ambient temperature:
+3 °C to +50 °C
Inlet temperature compressed air:
max. +60 °C
Refrigerant:
R-513a
Condensate drain:
Electronic steam trap, G 1/4" (F)
Operating voltage:
230V AC (alternating current)
Calculation of volume flow at non-reference conditions:
Volume flow = Volume flow at reference conditions x Kp x Kte x Ktu
Correction factor input pressure (Kp):
3 bar: Kp=0,64 - 4 bar: Kp=0,75 - 5 bar: Kp=0,84 - 6 bar: Kp=0,92 - 7 bar: Kp=1,00 - 8 bar: Kp=1,05 - 9 bar: Kp=1,09 - 10 bar: Kp=1,12 - 11 bar: Kp=1,16 - 12 bar: Kp=1,19 - 13 bar: Kp=1,22 - 14 bar: Kp=1,24 - 15 bar: Kp=1,26 - 16 bar: Kp=1,27
Correction factor compressed air inlet temperature (Kte):
+30°C: Kte=1,19 - +35°C: Kte=1,00 - +40°C: Kte=0,80 - +45°C: Kte=0,66 - +50°C: Kte=0,51 - +55°C: Kte=0,43 - +60°C: Kte=0,35
Ambient temperature correction factor (Ktu):
+25°C: Ktu=1,00 - +30°C: Ktu=0,96 - +35°C: Ktu=0,92 - +40°C: Ktu=0,88 - +45°C: Ktu=0,85 - +50°C: Ktu=0,80
*Performance data at reference conditions ISO 7183, option A: Operating pressure 7 bar, ambient temperature +25 °C, compressed air inlet temperature +35 °C.