Application:
For actuating smoke and heat exhausting systems such as roof flaps, skylight domes, skylights, louvers, top-hung, bottom-hung and side-hung windows. The cylinders are fitted with mechanical locking in both end positions. Thus, the respective position is retained even if there is a compressed air failure. The locking can be nullified even without compressed air with a manual emergency actuation.
Materials:
Body: Anodized aluminium, Swivel fastening: Steel, galvanized
Temperature range:
max. +100 °C
Operating pressure:
max. 30 bar
Pressure force at operating pressure:
6 bar: 361 N - 10 bar: 602 N - 15 bar: 903 N - 20 bar: 1,204 N - 25 bar: 1,505 N - 30 bar: 1,806 N