Electrical stainless steel ball valve, 42,4mm, 24 to 240 V (AC/DC)

Item number:

KH 114 ELI ES-AS

€931.13 incl. VAT
pcs
Item description
Advantages:
•2 additional limit switches,
•torque switch-off,
•variable voltage (DC or AC),
•manual emergency actuation,
•heating integrated in the actuator housing,
•length according to DIN 3202-M3 (weld ends according to DIN 3202-S13, EN 12982 ETE67)


Ball valve


Materials:
Body: 1.4408, ball: 1.4408, seal: PTFE / FKM

Temperature range:
-20 to +180 °C

Media:
Water, oil, compressed air, vacuum (max. -0.9 bar), fuels, solvents, aggressive media

Optional:
Welding ends -AS, certificate 3.1

Rotary actuator


Description:
Electrical rotary actuator with optical position indicator, manual emergency operation and switch room heating Two additional limit switches are installed for further control requirements. An electronic torque limiting unit prevents damage in the event of overload. The manual emergency operation can be done without dismantling the external cladding. Do not use upside down!

Materials:
Body: PA 6

Temperature range:
-20 to +70 °C

Voltage:
24 - 240 V AC/DC, (drives can be operated with direct or alternating voltage)

Protection class:
IP 67

Power-on time:
75%

Optional:
Regulating time 140 sec. (only for drive size 2 & 3) -140, "Battery Safety Return" for emergency closing NC (default configuration) or emergency opening NO (conversion with a jumper) when there is a power failure -BSR, Positioning system 0 - 10 V or 4 - 20 mA (conversion with a jumper), precision: 3%, linearity: 2%, hysteresis: 3%, switch position NC or NO (conversion with a jumper) -DPS

Warning:
In case of high media temperatures, the actuator must be cooled if necessary!
Properties
Ver­sion Stan­dard
De­sign Weld­ing ends
Volt­age [V] 24 to 240 V (AC/DC)
Weld­ing end di­am­e­ter [mm] 42,4
DN [mm] 32
In­stal­la­tion length ball valve [mm] 110
PN [bar] -0.9 to 63
Reg­u­lat­ing time [s] 9
Spare dri­ves ELU 230-2
Further information on KH114ELIES-AS
GTIN 4050571407407
Customs duty number 84818081
RoHS compliant Yes
Documents

 
All data are to be understood as non-binding reference values! We do not assume liability for any data selection not confirmed in writing. Unless otherwise specified, pressure values refer to liquids from Group II at +20°C.
Not in stock
Payment options:

Cash on delivery

Invoice