air consumption meter R 1", 14 to 3750 l/min

LVM 10

Exemplary representation: Air consumption meter (compressed air meter) detailed view: Air consumption meter (compressed air meter) IO-Link Schematic symbol: M 12 plug (A-coded, 4-pole)
1787,57€ incl. VAT
pcs
{{ $t('shop.display.artikel.hinweis_alternative') }}
{{ $t('shop.display.artikel.beschreibung_headline') }}
Application:
The consumption quantity, flow rate, flow velocity, operating pressure and media temperature of compressed air can be recorded and evaluated cost-effectively using the compressed air meter. Each device is equipped with two switching outputs, one of which can also be reprogrammed as an analogue or pulse output for external acquisition of the measured values. The peak consumption, cumulative consumption, instantaneous consumption can be read directly from the device. The unit of display and measurement can be toggled between Nl/min and Nm³/h.

Display:
pivoting TFT colour display with LED switching status indicator

Temperature range:
-10°C to +60°C, ambience: 0°C to +60°C

Protection class:
IP 67

Power supply:
18 - 30 V (DC)

Power input:
80 mA

Electrical connection:
M 12 connector, A-coded, 4-pin (DIN EN 61076-2-101) (plug)

Display unit:
Nl/min or Nm³/h

Measurement error:
Air class 141: ± 2% of reading or + 0.5% of the measuring range end value, air class 344: ± 6% of reading or + 0.6% of the measuring range end value

Pulse output:
1 Nl or 1 Nm³ per pulse (pulse duration adjustable 2 up to 2000 ms)

Control output (PNP/NPN):
2 switching outputs (normally open, normally closed, window and hysteresis freely adjustable for each switching output), max. 150 mA, output 1 can also be used for IO-Link, output 2 can also be used as analog output (4-20 mA) or pulse output.

Advantages:
•low procurement price, thus, the meter can be fixed permanently to the load,
•the smallest leaks are detected and can be quickly fixed,
•air consumption quantities can be assigned to production units,
•display for total consumption or current consumption at the site,
•switching, pulse or analogue output for external further processing,
•maintenance intervals can be determined depending on consumption,
•measurement free of pressure losses thanks to special design of the measurement sensors,
•exact measurement independent of pressure and temperature (max. +60°C),
•reading and saving of current process values and changing parameter settings possible via IO-link,
•red/green alternating display for clear marking of 'good' (OK) ranges
{{ $t('shop.display.artikel.eigenschaften_headline') }}
Thread R 1"
Measurement range [l/min] 14 - 3750
Measurement range [m³/h] 0,8 - 225
DN [mm] 25
length [mm] 475
Height (incl. tube) [mm] 84
Power supply LVM NETZ
LVM10
{{ $t('shop.all.gewicht') }} 1,5 kg / pcs
{{ $t('shop.all.gtin') }} 4050571469122
{{ $t('shop.display.artikel.zollwarennummer') }} 90262020
{{ $t('shop.all.dokumente') }}

 
{{ $t('shop.all.unverbindliche_richtwerte') }}

Accessories

Payment options:

{{ $t('shop.all.zahlweise_nachnahme') }}

{{ $t('shop.all.zahlweise.rg') }}

{{ $t('shop.all.spaetbestellservice') }}
{{ countdownAsString }} {{ $t('shop.modules.navi.fruehbucher-spaetbestellhinweis.noch') }}
{{ $t('shop.modules.navi.fruehbucher-spaetbestellhinweis.noch') }} {{ countdownAsString }}

{{ $t('shop.all.spaetbestellservice.hinweis') }}

{{ $t('shop.all.wochenendversand') }}
{{ $t('shop.modules.navi.fruehbucher-spaetbestellhinweis.noch') }} {{ countdownAsString }}

{{ $t('shop.all.wochenendversand.hinweis') }}

An error has occurred!

An error has occurred, please reload this page and try again.